Products and Services

 

IPSI
P.O. Box 92384
Rochester, New York 14692
In the USA
Tel. 1.800.959.4724
Fax: 585.359.9061
Contact IPSI

International
Tel. +001-585-334-5803
Fax. +001-585-359-9061

 
 

400 kW Natural Gas Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         400/500            360/450
Prime Power 105°C  350/438            325/406

Single Phase       
   60 Hz              50 Hz
                                   kW/KVA       kW/KVA
Continuous
Standby 150°C         275/275           318/318
Prime Power 105°C  241/241           261/261
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
400 kW Natural Gas Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

400 kW NG Generator Set
IPSI - Power On Wheels  
Engine Specifications
Manufacturer
Model
Type

4 Stroke V-12

Aspiration

Turbo/ After cooled

Cylinders 6
Displacement 1710 In³. (28 L)
Bore and Stroke 5.5 in x 6 in.

(140 mm x 152 mm)

Compression Ratio 10:1
Minimum C.C.A. at 5°C 1800
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 593 541
BMEP 153 psi 167 psi
Altitude and Ambient Temperature Requirements
The engine may be operated at the STANDBY RATING up to 3000 ft.(914m) altitude and 100°F (38°C) inlet air temperature and at the PRIME AND CONTINUOUS POWER RATING up to 5000 ft.(1524m) altitude and 100°F (38°C) inlet air temperature.  For sustained operation at high load factor at higher altitudes and temperatures, please contact IPSI.
Cooling System
High Ambient 117° F (47° C) System
Coolant Capacity with Radiator

43.5 US Gal. (165 L)

Maximum restriction on discharge side of
radiator

5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 214 GPM

195 GPM

(810 LPM)

(738 LPM)

Heat Rejection to Coolant at Rated

Full Load     34540 Btu/min

31535 Btu/min

Nat. Gas      (3644 MJ/min)

(3327 MJ/min)

Heat Rejection to Room at Rated

Full Load      4140 Btu/min

3780 Btu/min

Nat. Gas        (437 MJ/min)

(399 MJ/min)

Heat Rejection to Charge Air Cooler at Rated

Full Load       5300 Btu/min

4839 Btu/min

Nat. Gas        (559 MJ/min)

(511 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

15 In wc

14 In wc

(3.74 kPa)

(3.49 kPa)

Radiator Cooling Air Flow
74000 cfm

67562 cfm

(2094 m³/min)

(1912 m³/min)

Combustion Air Flow

1232 cfm

1175 cfm

(88 m³/min)

(80 m³/min)

Generator Cooling Air Flow

3104 cfm

2834 cfm

(87.8 m³/min)        (80 m³/min)

Exhaust System
Exhaust Outlet Size

dual 4 in. dia. (101.6 cm)

Maximum Allowable Back Pressure
2 in. wc (.5 kPa)
Exhaust Gas Flow at Standby Rating

4302 cfm

3928 cfm

(122 m³/min)

(111 m³/min)

Exhaust Temp at Standby Rating
1350°F

1233°F

(732°C)

(667°C)

Fuel System
Consumption at Standby Rating:
Load

1800 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 1979 (56.0)
1/2 3269 (92.5)
3/4 4423 (125.2)
Full 5551 (157.1)
Load

1500 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 1807 (51.1)
1/2 2985 (84.5)
3/4 4038 (114.3)
Full 5068 (143.4)
Governor Type Electronic
Governor Regulation:

+/- .25% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

1380 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

2540 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

2.77

2.59

Direct Axis Transient X'd

.260

.244

Direct Axis SubtransientX"d

.144

.244

Negative Sequence X2

.159

.149

Zero Sequence Xo

.0034

.0032

Lubrication System
Engine Oil Capacity with Filters

29.7 qts. (28.22L)

Oil Filter Type

Spin On

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        

     Site Created by Amy Pschierer