300 kW Natural Gas Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         300/375            280/350
Prime Power 105°C  275/344            255/319

Single Phase       
   60 Hz              50 Hz
                                   kW/KVA       kW/KVA
Continuous
Standby 150°C         235/235           241/241
Prime Power 105°C  201/201           201/201
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
300 kW Natural Gas Generator Set

Product Features

System Reliability and Longevity
begin with design experience and integrity.

.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.





Technical Specifications

300 kW NG Generator Set
IPSI - Power On Wheels  
Engine Specifications
Manufacturer
Model
Type

4 Cycle

Aspiration

Turbo/ After cooled

Cylinders 6
Displacement 1150 In³. (19 L)
Bore and Stroke 6.25 in x 6.25 in.

(159 mm x 159 mm)

Compression Ratio 10:1
Minimum C.C.A. at 5°C 900
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 452 413
BMEP 173 psi 190 psi
Altitude and Ambient Temperature Requirements
The engine may be operated at the STANDBY RATING up to 3000 ft.(914m) altitude and 100°F (38°C) inlet air temperature and at the PRIME AND CONTINUOUS POWER RATING up to 5000 ft.(1524m) altitude and 100°F (38°C) inlet air temperature.  For sustained operation at high load factor at higher altitudes and temperatures, please contact IPSI.
Cooling System
High Ambient 117° F (47° C) System
Coolant Capacity with Radiator

33.25 US Gal. (126  L)

Maximum restriction on discharge side of
radiator

5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 189 GPM

173 GPM

(717 LPM)

(655 LPM)

Heat Rejection to Coolant at Rated

Full Load     20473 Btu/min

18692 Btu/min

Nat. Gas      (2160 MJ/min)

(1972 MJ/min)

Heat Rejection to Room at Rated

Full Load      2459 Btu/min

2245 Btu/min

Nat. Gas        (259 MJ/min)

(237 MJ/min)

Heat Rejection to Charge Air Cooler at Rated

Full Load       3200 Btu/min

2922 Btu/min

Nat. Gas        (338 MJ/min)

(308 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

15 In wc

14 In wc

(3.74 kPa)

(3.49 kPa)

Radiator Cooling Air Flow
40000 cfm

36520 cfm

(1132 m³/min)

(1034 m³/min)

Combustion Air Flow

713 cfm

651 cfm

(20 m³/min)

(18 m³/min)

Generator Cooling Air Flow

3104 cfm

2834 cfm

(87.8 m³/min)        (80 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

5 in. dia. (127 mm)

Maximum Allowable Back Pressure
2 in. wc (.5 kPa)
Exhaust Gas Flow at Standby Rating

2495 cfm

2278 cfm

(71 m³/min)

(64 m³/min)

Exhaust Temp at Standby Rating
1350°F

1233°F

(732°C)

(667°C)

Fuel System
Consumption at Standby Rating:
Load

1800 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 1176 (33..3)
1/2 1943 (55.0)
3/4 2624 (74.3)
Full 3291 (93.1)
Load

1500 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 1074 (30.4)
1/2 1774 (50.2)
3/4 2396 (67.8)
Full 3005 (85.0)
Governor Type Electronic
Governor Regulation:

+/- .25% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

790 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

1080 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.13

2.91

Direct Axis Transient X'd

.305

.283

Direct Axis SubtransientX"d

.175

.162

Negative Sequence X2

.189

.176

Zero Sequence Xo

.0038

.0035

Lubrication System
Engine Oil Capacity with Filters

64 qts. (61 L)

Oil Filter Type

Spin On

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        