250 kW Natural Gas Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         250/313            240/300
Prime Power 105°C  210/263            200/250

Single Phase       
   60 Hz              50 Hz
                                   kW/KVA       kW/KVA
Continuous
Standby 150°C         188/188           174/174
Prime Power 105°C  161/161           151/151
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
250 kW Natural Gas Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

250 kW NG\ LP Generator Set
IPSI - Power On Wheels  
Engine Specifications
Manufacturer
Model
Aspiration

Turbo/ After cooled

Cylinders 6
Displacement 855 In³. (14 L)
Bore and Stroke 5.5 in x 6 in.

(140 mm x 152 mm)

Compression Ratio 11:1
Minimum C.C.A. at 5°C 900
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 385 352
BMEP 198 psi 217 psi
Altitude and Ambient Temperature Requirements
The engine may be operated at the STANDBY RATING up to 3000 ft.(914m) altitude and 100°F (38°C) inlet air temperature and at the PRIME AND CONTINUOUS POWER RATING up to 5000 ft.(1524m) altitude and 100°F (38°C) inlet air temperature.  For sustained operation at high load factor at higher altitudes and temperatures, please contact IPSI.
Cooling System
High Ambient 117° F (47° C) System
Coolant Capacity with Radiator

30.5 US Gal. (115.5 L)

Maximum restriction on discharge side of
radiator

5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 113 GPM

103 GPM

(428 LPM)

(390 LPM)

Heat Rejection to Coolant at Rated

Full Load     14308 Btu/min

13063 Btu/min

Nat. Gas      (1509 MJ/min)

(1378 MJ/min)

Heat Rejection to Room at Rated

Full Load      1615 Btu/min

1474 Btu/min

Nat. Gas        (170 MJ/min)

(156 MJ/min)

Heat Rejection to Charge Air Cooler at Rated

Full Load       1846 Btu/min

1685 Btu/min

Nat. Gas        (195 MJ/min)

(178 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

15 In wc

14 In wc

(3.74 kPa)

(3.49 kPa)

Radiator Cooling Air Flow
37000 cfm

33781 cfm

(1047 m³/min)

(956 m³/min)

Combustion Air Flow

854 cfm

780 cfm

(24 m³/min)

(22 m³/min)

Generator Cooling Air Flow

3104 cfm

2834 cfm

(87.8 m³/min)          (80 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

4 in. dia. (102 cm)

Maximum Allowable Back Pressure
2 in. wc (.5 kPa)
Exhaust Gas Flow at Standby Rating

2478 cfm

2262 cfm

(70 m³/min)

(64 m³/min)

Exhaust Temp at Standby Rating
1350°F

1233°F

(732°C)

(667°C)

Fuel System
Consumption at Standby Rating:
Load

1800 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 1030 (29.1)
1/2 1720 (48.7)
3/4 2372 (67.1)
Full 3037 (86.0)
Load

1500 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 940 (26.6)
1/2 1570 (44.4)
3/4 2166 (61.3)
Full 2773 (78.5)
Governor Type Electronic
Governor Regulation:

+/- .25% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

288 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

599 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.09

2.75

Direct Axis Transient X'd

.233

.207

Direct Axis SubtransientX"d

.154

.137

Negative Sequence X2

.165

.147

Zero Sequence Xo

.0026

.0023

Lubrication System
Engine Oil Capacity with Filters

44 qts. (41.6 L)

Oil Filter Type

Spin On

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        