Products and Services

 

IPSI
P.O. Box 92384
Rochester, New York 14692
In the USA
Tel. 1.800.959.4724
Fax: 585.359.9061
Contact IPSI

International
Tel. +001-585-334-5803
Fax. +001-585-359-9061

 
 

180 kW Natural Gas Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         180/225            162/202
Prime Power 105°C  162/202            146/182

Single Phase       
   60 Hz              50 Hz
                                   kW/KVA       kW/KVA
Continuous
Standby 150°C         127/127           141/141
Prime Power 105°C  107/107           127/127
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.

180 kW Natural Gas Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.


Technical Specifications

180 kW NG Generator Set
IPSI - Power On Wheels  
Engine Specifications
Manufacturer
Model
Type 4 cycle, In line
Aspiration

Turbo/ After cooled

Cylinders 6
Displacement 743 In³. (12 L)
Bore and Stroke 5.13 in x 6 in.

(130.3 mm x 152 mm)

Compression Ratio 8.5:1
Minimum C.C.A. at 5°C 1800
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 280 256
BMEP 166 psi 182 psi
Altitude and Ambient Temperature Requirements
The engine may be operated at the STANDBY RATING up to 3000 ft.(914m) altitude and 100°F (38°C) inlet air temperature and at the PRIME AND CONTINUOUS POWER RATING up to 5000 ft.(1524m) altitude and 100°F (38°C) inlet air temperature.  For sustained operation at high load factor at higher altitudes and temperatures, please contact IPSI.
Cooling System
High Ambient 117° F (47° C) System
Coolant Capacity with Radiator

25 US Gal. (94.6 L)

Maximum restriction on discharge side of
radiator

5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 87 GPM

79 GPM

(330 LPM)

(299 LPM)

Heat Rejection to Coolant at Rated

Full Load     11825 Btu/min

10796 Btu/min

Nat. Gas      (1248 MJ/min)

(1139 MJ/min)

Heat Rejection to Room at Rated

Full Load     11825 Btu/min

10796 Btu/min

Nat. Gas        (154 MJ/min)

(1139 MJ/min)

Heat Rejection to Charge Air Cooler at Rated

Full Load       1800 Btu/min

1643 Btu/min

Nat. Gas      (1906 MJ/min)

(173 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

15 In wc

14 In wc

(3.74 kPa)

(3.49 kPa)

Radiator Cooling Air Flow
23500 cfm

21456 cfm

(665 m³/min)

(607 m³/min)

Combustion Air Flow

420 cfm

383 cfm

(12 m³/min)

(11 m³/min)

Generator Cooling Air Flow

2348 cfm

2144 cfm

(66.4 m³/min)   (60.7 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

4.0 in. dia. (102 cm)

Maximum Allowable Back Pressure
2 In wc (.5 kPa)
Exhaust Gas Flow at Standby Rating

1385 cfm

1274 cfm

(39.5 m³/min)

(36.1 m³/min)

Exhaust Temp at Standby Rating
1350°F

1233°F

(732°C)

(667°C)

Fuel System
Consumption at Standby Rating:
Load

1800 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 564 (16.0)
1/2 961 (27.2)
3/4 1324 (37.5)
Full 1677 (47.5)
Load

1500 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 515 (14.6)
1/2 877 (24.8)
3/4 1209 (34.2)
Full 1531 (43.3)
Governor Type Electronic
Governor Regulation:

+/- .25% Steady State

Generator

Model

1

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

346 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

780 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

4.27

4.1

Direct Axis Transient X'd

.449

.431

Direct Axis SubtransientX"d

.274

.263

Negative Sequence X2

.286

.275

Zero Sequence Xo

.0052

.0049

Lubrication System
Engine Oil Capacity with Filters

46 qts. (44 L)

Oil Filter Type

Spin On

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        