150 kW Natural Gas Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         150/187            135/168
Prime Power 105°C  135/168            122/152

Single Phase       
   60 Hz              50 Hz
                                   kW/KVA       kW/KVA
Continuous
Standby 150°C         96/96                107/107
Prime Power 105°C  80/80                   80/80
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
150 kW Natural Gas Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

150 kW NG Generator Set
IPSI - Power On Wheels  
Engine Specifications
Manufacturer
Model
Type 4 cycle, In line
Aspiration

Turbo/ After cooled

Cylinders 6
Displacement 504.5 In³. (8.3 L)
Bore and Stroke 4.49 in x 5.32 in.

(114 mm x 135 mm)

Compression Ratio 10.5:1
Minimum C.C.A. at 5°C 900
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 228 208
BMEP 199 psi 218 psi
Altitude and Ambient Temperature Requirements
The engine may be operated at the STANDBY RATING up to 3000 ft.(914m) altitude and 100°F (38°C) inlet air temperature and at the PRIME AND CONTINUOUS POWER RATING up to 5000 ft.(1524m) altitude and 100°F (38°C) inlet air temperature.  For sustained operation at high load factor at higher altitudes and temperatures, please contact IPSI.
Cooling System
High Ambient 105° F (41° C) System
Coolant Capacity with Radiator

28 US Gal. (86.6 L)

Maximum restriction on discharge side of
radiator

5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 55 GPM

50 GPM

(208 LPM)

(189 LPM)

Heat Rejection to Coolant at Rated

Full Load       7619 Btu/min

6956 Btu/min

Nat. Gas        (804 MJ/min)

(734 MJ/min)

Heat Rejection to Room at Rated

Full Load         952 Btu/min

869 Btu/min

Nat. Gas        (100 MJ/min)

(92 MJ/min)

Heat Rejection to Charge Air Cooler at Rated

Full Load         816 Btu/min

745 Btu/min

Nat. Gas          (86 MJ/min)

(79 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

25 In wc

25 In wc

(6.25 kPa)

(6.25 kPa)

Radiator Cooling Air Flow
16000 cfm

14608 cfm

(453 m³/min)

(413 m³/min)

Combustion Air Flow

513 cfm

468 cfm

(15 m³/min)

(13 m³/min)

Generator Cooling Air Flow

2348 cfm

2144 cfm

(66.4 m³/min)   (60.7 m³/min)

Exhaust System
Exhaust Outlet Size

3.5 in. dia. (89 mm)

Maximum Allowable Back Pressure
2 In wc (.5 kPa)
Exhaust Gas Flow at Standby Rating

1485 cfm

1356 cfm

(42 m³/min)

(38 m³/min)

Exhaust Temp at Standby Rating
1100°F

1004°F

(593°C)

(540°C)

Fuel System
Consumption at Standby Rating:
Load

1800 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 555 (15.7)
1/2 912 (25.8)
3/4 1314 (42.8)
Full 1728(48.9)
Load

1500 RPM

Natural Gas

C.F.H.(Cu.M./Hr.)

1/4 515 (14.3)
1/2 877 (23.6)
3/4 1200 (34)
Full 1531 (44.7)
Governor Type Mechanical
Governor Regulation:

+/- .5% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

360 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

790 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.11

2.63

Direct Axis Transient X'd

.231

.196

Direct Axis SubtransientX"d

.151

.128

Negative Sequence X2

.198

.168

Zero Sequence Xo

.0027

.0023

Lubrication System
Engine Oil Capacity with Filters

32 qts. (34.1 L)

Oil Filter Type

Spin On

                                      

 