Products and Services

 

IPSI
P.O. Box 92384
Rochester, New York 14692
In the USA
Tel. 1.800.959.4724
Fax: 585.359.9061
Contact IPSI

International
Tel. +001-585-334-5803
Fax. +001-585-359-9061

 
 

780 kW Diesel Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         780/975           690/863
Prime Power 105°C  695/869           625/781

Single Phase       
    60 Hz              50 Hz
                                    kW/KVA       kW/KVA
Continuous
Standby 150°C          482/482          536/536
Prime Power 105°C    415/415          456/456
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
780 kW Diesel Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications
780 kW Diesel Generator Set
Integrated Power Systems International, Inc.  
Engine Specifications
Manufacturer

Model

Type

In line 4 Stroke

Aspiration

Turbo/ Water to Air After cooled

Cylinders

60° V12

Displacement

2070 In³. (33.93L)

Bore and Stroke

5.91 in x 6.30 in.

(150 mm x 160 mm)

Compression Ratio

14.5:1

Minimum C.C.A. at 5°C

300 Ah

RPM

1800 rpm

1500 rpm

BHP Minimum REQ"D at Rated kW

1100

970

BMEP

233 psi

247 psi

General Set Deration Factors
Temperature:
  4% for every 18° F above 104° F
  4% for every 10° C above 40° C
Altitude

  2.5% for every 383 feet above 4918 feet

  2.5% for every 167 meters above 1499 meters

Cooling System
High Ambient 104° F (40° C) System
Coolant Capacity with Radiator

55.4 qt. (210L)

Maximum restriction on discharge side of
radiator

.5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow

291 GPM

264 GPM

(1102 LPM)

(1000 LPM)

Heat Rejection to Coolant at Full Load

29797 Btu/min

25480 Btu/min

(3144 MJ/min)

(2688 MJ/min)

Heat Rejection to Room at Rated Full Load

3705 Btu/min

3169 Btu/min

(391 MJ/min)

(334 MJ/min)

Air System
Maximum Air Intake

1800 rpm

1500 rpm

Restriction

25.0 In wc

(6.2 kPa)

Radiator Cooling Air Flow

48278 cfm

40253 cfm

(1366 m³/min)

(1139 m³/min)

Combustion Air Flow

2613 cfm

2260 cfm

(73.9 m³/min)

(64.0 m³/min)

Generator Cooling Air Flow

5256 cfm

4380 cfm

(148.7 m³/min)   (124 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

8.35 in. dia. (21.2 cm)

Maximum Allowable Back Pressure

17.7 In wc (5.9 kPa)

Exhaust Gas Flow at Standby Rating

6956 cfm

5932 cfm

(196.9 m³/min)(167.9 m³/min)

Exhaust Temp at Standby Rating
950°F

842°F

(510°C)

(450°C)

Fuel System
Consumption at Standby Rating:
Load

  1800 RPM

kW

US gal/h Litre/h
1/4

195

18.5 70
1/2

390

29.0 110
3/4 585 43.6 165
Full 780 58.1 220
Load

  1500 RPM

kW

US gal/h Litre/h
1/4

173

13.2 50
1/2

345

24.6 93
3/4 518 37.0 140
Full 690 48.9 185
Governor Type

Electric

Governor Regulation:

+/- .2%

Generator

Model

.

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

1744 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

3833 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.52

3.38

Direct Axis Transient X'd

.280

.269

Direct Axis SubtransientX"d

.190

.182

Zero Sequence Xo

.0107

.0103

Lubrication System
Engine Oil Capacity with Filters

26.4 US gal. (100L)

Oil Filter Type

Spin On

Engine Exhaust Emissions
Certification Values
Exhaust Emissions (g/bhp-hr.)

*ARB

780RD

THC: 1

.4

CO: 8.5

.4

NOx: 6.9

6.3

PM: .4

.2

Smoke Opacit y (%)
Acceleration: 20

N/A

Lugging 15

2

Peak 50

N/A

* California Air Resources Board Standards.
Dimensions:
X Axis:

XX"

Y Axis:

XX"

Z Axis:

XX"

.
Dry Weight (estimated):

XXXXLbs

 

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        

     Site Created by Amy Pschierer