Products and Services

 

IPSI
P.O. Box 92384
Rochester, New York 14692
In the USA
Tel. 1.800.959.4724
Fax: 585.359.9061
Contact IPSI

International
Tel. +001-585-334-5803
Fax. +001-585-359-9061

 
 

600 kW Diesel Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA        kW/KVA

Continuous
Standby 150°C         600/750           524/655
Prime Power 105°C  540/675            472/590

Single Phase       
    60 Hz              50 Hz
                                    kW/KVA       kW/KVA
Continuous
Standby 150°C          358/358          409/409
Prime Power 105°C    308/308          348/348
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
600 kW Diesel Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

600 kW Diesel Generator Set
Integrated Power Systems International, Inc.  
Engine Specifications
Manufacturer

Model

Type

In line 4 Stroke

Aspiration

Turbo/ Water to Air After cooled

Cylinders

6

Displacement

1496 In³. (33.93L)

Bore and Stroke

6.69 in x 7.09 in.

(170 mm x 180 mm)

Compression Ratio

14.0:1

Minimum C.C.A. at 5°C

200 Ah

RPM

1800 rpm

1500 rpm

BHP Minimum REQ"D at Rated kW

851

744

BMEP

259 psi

270 psi

General Set Deration Factors
Temperature:
  4% for every 18° F above 104° F
  4% for every 10° C above 40° C
Altitude

  2.5% for every 383 feet above 4918 feet

  2.5% for every 167 meters above 1499 meters

Cooling System
High Ambient 104° F (40° C) System
Coolant Capacity with Radiator

40.2 qt. (152L)

Maximum restriction on discharge side of
radiator

.5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow

211 GPM

177 GPM

(798.7 LPM)

(670 LPM)

Heat Rejection to Coolant at Full Load

21650 Btu/min

18462 Btu/min

(2284 MJ/min)

(1948 MJ/min)

Heat Rejection to Room at Rated Full Load

2692 Btu/min

2296 Btu/min

(284 MJ/min)

(242 MJ/min)

Air System
Maximum Air Intake

1800 rpm

1500 rpm

Restriction

25 In wc

(6.2 kPa)

Radiator Cooling Air Flow

25423 cfm

20550 cfm

(719 m³/min)

(582 m³/min)

Combustion Air Flow

1907 cfm

1624 cfm

(54.0 m³/min)

(46.0 m³/min)

Generator Cooling Air Flow

5256 cfm

4380 cfm

(148.7 m³/min)    (124 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

8.35 in. dia. (21.2cm)

Maximum Allowable Back Pressure

23.6 In wc (5.9 kPa)

Exhaust Gas Flow at Standby Rating

5049 cfm

4308 cfm

(142.89 m³/min)(1121.91 m³/min)

Exhaust Temp at Standby Rating
1022°F

1094°F

(550°C)

(590°C)

Fuel System
Consumption at Standby Rating:
Load

  1800 RPM

kW

US gal/h Litre/h
1/4

150

12.7 48
1/2

300

23.3 88
3/4 450 31.7 120
Full 600 42.3 160
Load

  1500 RPM

kW

US gal/h Litre/h
1/4

131

10.3 39
1/2

262

17 64
3/4 450 31.7 120
Full 600 42.3 160
Governor Type

Electric

Governor Regulation:

+/- .2%

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

1080 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

3947 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.89

4.09

Direct Axis Transient X'd

.332

.316

Direct Axis SubtransientX"d

.240

.228

Zero Sequence Xo

.0136

.0129

Lubrication System
Engine Oil Capacity with Filters

21.1 US gal. (80L)

Oil Filter Type

Spin On

Engine Exhaust Emissions
Certification Values
Exhaust Emissions (g/bhp-hr.)

*ARB

600RD

THC: 1

.4

CO: 8.5

.4

NOx: 6.9

6.3

PM: .4

.2

Smoke Opacit y (%)
Acceleration: 20

N/A

Lugging 15

2

Peak 50

N/A

* California Air Resources Board Standards.
Dimensions:
X Axis:

XX"

Y Axis:

XX"

Z Axis:

XX"

.
Dry Weight (estimated):

XXXXLbs

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        