30 kW Diesel Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA         kW/KVA

Continuous
Standby 150°C         30/37                27/33
Prime Power 105°C  27/33                24/30

Single Phase       
    60 Hz              50 Hz
                                    kW/KVA       kW/KVA
Continuous
Standby 150°C           17/17             19/19
Prime Power 105°C    14/14              16/16
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.

30 kW Diesel Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.


Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications
30 kW Diesel Generator Set
Integrated Power Systems International, Inc.  
Engine Specifications
Manufacturer

Model

Type

In line 4 Stroke

Aspiration

Natural

Cylinders

4

Displacement

171 In³. (2.8 L)

Bore and Stroke

3.66 in x 4.02 in.

(93 mm x 102 mm)

Compression Ratio

18.2:1

Minimum C.C.A. at 5°C

650

RPM

1800 rpm

1500 rpm

BHP Minimum REQ"D at Rated kW

48

43

BMEP

124 psi

133 psi

General Set Deration Factors
Temperature:
  2.5% for every 5° F above 105° F
  2.5% for every 9° C above 41° C
Altitude

  3% for every 1000 feet above 600 feet

  3% for every 305 meters above 183 meters

Cooling System
High Ambient 105° F (41° C) System
Coolant Capacity with Radiator

10 qt. (9.5 L)

Maximum restriction on discharge side of
radiator

.5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow

39 GPM

32 GPM

(147.6 LPM)

(121.1 LPM)

Heat Rejection to Coolant at Full Load

1820 Btu/min

1638 Btu/min

(192 MJ/min)

(173 MJ/min)

Heat Rejection to Room at Rated Full Load

1820 Btu/min

1638 Btu/min

(192 MJ/min)

(173 MJ/min)

Air System
Maximum Air Intake

1800 rpm

1500 rpm

Restriction

30 In wc

(7.5 kPa)

Radiator Cooling Air Flow

3750 cfm

3500 cfm

(106.1 m³/min)

(99.1 m³/min)

Combustion Air Flow

107 cfm

96 cfm

(3.0 m³/min)

(2.7 m³/min)

Generator Cooling Air Flow

453 cfm

378 cfm

(12.8 m³/min)      (10.7 m³/min)

Exhaust System
Exhaust Outlet Size

1.8 in. dia. (4.5 cm)

Maximum Allowable Back Pressure

40.9 In wc (10.2 kPa)

Exhaust Gas Flow at Standby Rating

3113 cfm

286 cfm

(9 m³/min)

(8.1 m³/min)

Exhaust Temp at Standby Rating
1060°F

954°F

(571°C)

(512°C)

Fuel System
Consumption at Standby Rating:
Load

  1800 RPM

kW

US gal/h Litre/h
1/4

7.5

.6 2.27
1/2

15

1.1 4.16
3/4 22.5 1.6 6.1
Full 30 2.2 8.33
Load

  1500 RPM

kW

US gal/h Litre/h
1/4

6.75

.54 2
1/2

13.5

1 3.8
3/4 20.75 1.44 5.5
Full 27 1.98 7.5
Governor Type

Mechanical

Governor Regulation:

+/- 3-5% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

45 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

149 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

4.08

3.72

Direct Axis Transient X'd

.31

.286

Direct Axis SubtransientX"d

.241

.222

Zero Sequence Xo

.0040

.0037

Lubrication System
Engine Oil Capacity with Filters

2.25 US gal. (8.5 L)

Oil Filter Type

Spin On

Engine Exhaust Emissions
Certification Values
Exhaust Emissions (g/bhp-hr.)

*ARB

50RD

THC: 1

.4

CO: 4.8

1

NOx: 6.9

6.2

PM: .63

.19

Smoke Opacit y (%)
Acceleration: 20

3

Lugging 15

3

Peak 50

6

* California Air Resources Board Standards.
Dimensions:
X Axis:

XX"

Y Axis:

XX"

Z Axis:

XX"

Weight:

XXXX

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        