Products and Services

 

IPSI
P.O. Box 92384
Rochester, New York 14692
In the USA
Tel. 1.800.959.4724
Fax: 585.359.9061
Contact IPSI

International
Tel. +001-585-334-5803
Fax. +001-585-359-9061

 
 

10 kW Diesel Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA         kW/KVA

Continuous
Standby 150°C         10/12                9/11
Prime Power 105°C   9/11                 8/10

Single Phase       
    60 Hz              50 Hz
                                    kW/KVA       kW/KVA
Continuous
Standby 150°C           8/8                  9/9
Prime Power 105°C    7/7                  7/7
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
10 kW Diesel Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

10 kW Diesel Generator Set
Integrated Power Systems International, Inc.  
Engine Specifications
Manufacturer
Model
Type In line 4 Stroke
Aspiration Natural
Cylinders 3
Displacement 67 In³. (1.1 L)
Bore and Stroke 3.05 in x 3.14 in.

(77.4 mm x 79.7 mm)

Compression Ratio 22:1
Minimum C.C.A. at 5°C 580
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D
at Rated kW 18 16
BMEP 118 psi 126 psi
General Set Deration Factors
Temperature:
  2.5% for every 5° F above 105° F
  2.5% for every 9° C above 41° C
Altitude
  3% for every 1000 feet above 600 feet
  3% for every 305 meters above 183 meters
Cooling System
High Ambient 105° F (41° C) System
Coolant Capacity with Radiator

5 qt.  (4.7 L)

Maximum restriction on discharge side of
radiator

.5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 9.5 GPM

8 GPM

(36 LPM)

(30.3 LPM)

Heat Rejection to Coolant at Full Load

Full Load      730 Btu/min

650 Btu/min

(77 MJ/min) 

(69 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

30 In wc

(7.5 kPa)

Radiator Cooling Air Flow
2100 cfm

1850 cfm

(59.4 m³/min)

(52.4 m³/min)

Combustion Air Flow

453 cfm

378 cfm

(1.7 m³/min)

(1.4 m³/min)

Generator Cooling Air Flow

453 cfm

378 cfm

   (12.8 m³/min)       (10.7 m³/min)

Exhaust System
Exhaust Outlet Size

1.8 in. dia. (4.5 cm)

Maximum Allowable Back Pressure
40.9 In wc (10.2 kPa)
Exhaust Gas Flow at Standby Rating

80 cfm

72 cfm

(2.3 m³/min)

(2 m³/min)

Exhaust Temp at Standby Rating
890°F

801°F

(477°C)

(427°C)

Fuel System
Consumption at Standby Rating:
Load

  1800 RPM

kW

US gal/h Litre/h
1/4

2.5

.21 .79
1/2

5

.42 1.6
3/4 7.5 .63 2.4
Full 10 .85 3.2
Load

  1500 RPM

kW

US gal/h Litre/h
1/4

2.25

.19 .72
1/2

4.5

.38 1.4
3/4 6.75 .57 2.2
Full 9 .77 2.9
Governor Type Mechanical
Governor Regulation:

+/- 3-5% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

29.5 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

45 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

      2.48

2.38

Direct Axis Transient X'd

.219

.210

Direct Axis SubtransientX"d

.182

.174

Zero Sequence Xo

.0024

.0023

Lubrication System
Engine Oil Capacity with Filters

1.23 US gal. (4.7L)

Oil Filter Type

Spin On

Engine Exhaust Emissions
Certification Values
Exhaust Emissions (g/bhp-hr.)

*ARB

50RD

HC + NOx 10

7.5

CO 350

1

PM .9

.2

* California Air Resources Board Standards.
Dimensions:
X Axis:

XX"

Y Axis:

XX"

Z Axis:

XX"

Weight:

XXXX

                                      

 

                             Electrical Generating Systems Association             National Fire Protection Association        

     Site Created by Amy Pschierer