100 kW Diesel Generator Set

Integrated Power Systems International, Inc.

Generator Set Rating
Three Phase             60 Hz               50 Hz
                                   kW/KVA         kW/KVA

Continuous
Standby 150°C         100/125             90/112
Prime Power 105°C  90/112               81/101

Single Phase       
    60 Hz              50 Hz
                                    kW/KVA       kW/KVA
Continuous
Standby 150°C           60/60             67/67
Prime Power 105°C    50/50             61/61
Quality Power Producing Equipment
is our business at Integrated Power Systems International Inc. Our power systems offer solutions to requirements for reliable, Quality electrical power.
* 100% full load tested.
* Performance supported by prototype testing.
* 12 lead re-connectable AC synchronous generators.
* Solid state automatic voltage regulator.
* 50 or 60 Hz operational.
* Standard Digital Control Panel meeting standards set by NFPA-110.
100 kW Diesel Generator Set
Product Features

System Reliability and Longevity
begin with design experience and integrity.

Single Source Responsibility:
Product services support and parts available through IPSI.

Accessories and Flexibility
are designed into IPSI generator sets at the factory level to meet specific application needs.

Organizational Commitment
to innovative, leading edge technology and environmentally friendly electrical products and services.



Technical Specifications

100 kW Diesel Generator Set
>
Integrated Power Systems International, Inc.  
Engine Specifications
Manufacturer
Model
Type In line 4 Stroke
Aspiration Turbo
Cylinders 6
Displacement 396 In³. (6.5 L)
Bore and Stroke 4.13 in x 4.92 in.

(105 mm x 125 mm)

Compression Ratio 17.5:1
Minimum C.C.A. at 5°C 780
RPM

1800 rpm

1500 rpm
BHP Minimum REQ"D at Rated kW
154 139
BMEP 171 psi 185 psi
General Set Deration Factors
Temperature:
  2.5% for every 5° F above 105° F
  2.5% for every 9° C above 41° C
Altitude
  2% for every 2000 feet above 2000 feet
  2% for every 607 meters above 607 meters
Cooling System
High Ambient 105° F (41° C) System
Coolant Capacity with Radiator

24 qt.  (22.7 L)

Maximum restriction on discharge side of
radiator

.5 In wc (125 Pa)

1800 rpm

1500 rpm

Coolant Flow 52 GPM

43 GPM

(196.8 LPM)

(162.8 LPM)

Heat Rejection to Coolant at Full Load

Full Load       4050 Btu/min

3645 Btu/min

             (427 MJ/min)

(385 MJ/min)

Air System
Maximum Air Intake
1800 rpm

1500 rpm

Restriction

30 In wc

(7.5 kPa)

Radiator Cooling Air Flow
8000 cfm

7200 cfm

(226.4 m³/min)

(203.8 m³/min)

Combustion Air Flow

337 cfm

288 cfm

(7.8 m³/min)

(7 m³/min)

Generator Cooling Air Flow

2348 cfm

1957 cfm

  (66.4 m³/min)      (55.4 m³/min)

Exhaust System
Exhaust Manifold Outlet Size

3.0 in. dia. (7.6 cm)

Maximum Allowable Back Pressure
40.9 In wc (10.2 kPa)
Exhaust Gas Flow at Standby Rating

680 cfm

612 cfm

(19.2 m³/min)

(10.2 m³/min)

Exhaust Temp at Standby Rating
1150°F

1200°F

(621°C)

(649°C)

Fuel System
Consumption at Standby Rating:
Load

  1800 RPM

kW

US gal/h Litre/h
1/4

25

1.7 6.4
1/2

50

3.3 12.5
3/4 75 5 18.9
Full 100 6.5 24.6
Load

  1500 RPM

kW

US gal/h Litre/h
1/4

22.5

1.4 5.3
1/2

45

2.7 10.22
3/4 67.5 4.1 15.5
Full 90 5.5 20.8
Governor Type Mechanical
Governor Regulation:

+/- 3-5% Steady State

Generator

Model

Motor Starting KVA, 240/480 Volt WYE at
35% Voltage Dip, 100% Voltage Recovery

318 SKVA

Maximum Motor Starting KVA, 35%
Voltage Dip Oversized Generator

346 SKVA

Reactances

480V

400V

at 105°C rise

60Hz

50Hz

Synchronous Xd

3.78

3.75

Direct Axis Transient X'd

.293

.291

Direct Axis SubtransientX"d

.198

.197

Zero Sequence Xo

.0032

.0032

Lubrication System
Engine Oil Capacity with Filters

4.63 US gal. (17.5L)

Oil Filter Type

Spin On

Engine Exhaust Emissions
Certification Values
Exhaust Emissions (g/bhp-hr.)

*ARB

100RD

THC: 1

.5

CO: 3.7

.5

NOx: 6.9

5.7

PM: .52

.17

* California Air Resources Board Standards.
Dimensions:
X Axis:

XX"

Y Axis:

XX"

Z Axis:

XX"

Weight:

XXXX

                                      

 