RST Series Automatic Transfer Panels
Tech Specs
Transfer Panel Mechanism

*Transfer Action
Independent break-before-make action positively prevents dangerous source-to source connections.

*Mechanical Interlock
Prevents simultaneous closing of normal and emergency contacts.

*Surge Withstand Ratings
Guidelines for location. Surge test waveforms for location category B3, per IEEE C62.41. Testing per guidelines in IEEE C62.45

*Electrical Interlocks
Prevents simultaneous closing signals to normal and emergency contacts and interconnection of normal and emergency sources through the control wiring.

*Environmental
--Operating Temperatures: -40 degrees F to 122 degrees F
--Storage Temperatures: 140 degrees F to 140 degrees F
--Humidity: 95% relative humidity, non-condensing
--Altitude: up to 10,000 ft without derating.

Control Features

Start Time Delay: 3 sec., Prevents nuisance generator set starts during momentary utility power variations.

Transfer Time Delay: 3 sec., Allows generator set to stabilize before load is applied.

Retransfer Time Delay: 5 min., Prevents needless power interruption if return of utility power is momentary.

Stop Time Delay: 5 min., Allows for gradual generator set cool down.

Undervoltage Sensing: Normal & Emergency:
-Pickup: 85% of nominal
-Dropout: 75% of pickup
Provides reliable sensing of utility power to start the generator set in brownout conditions. Reliably maintains connection through motor starting voltage dips.

UL Withstand and Closing Ratings
The RST transfer panel must be protected by an overcurrent device of the type and size specified which will protect the switch when used on a circuit capable of delivering not more than the symmetrical RMS amperes listed in the table.

WCR Ratings using Current Limiting Fuses

Switch Amp Rating WCR @max voltage with
Current Limiting Fuse
Max Fuse Size
and Type
60A 100,000 A (600VAC) 100A, Class J or T
100A 100,000 A (600VAC) 225 A, Class J or T
200A 100,000 A (600VAC) 400 A, Class J or T
 
Transfer Panel Lug Capacities
Switch Amp Rating Size
60 2 to 10 AWG CU
100 2/0 to 14 AWG CU/AL
200 300 MCM to 6 AWG CU/AL
WCR Ratings using specific circuit breakers
WCR Ratings using specific manufacturers circuit breakers, contact IPSI

Transfer Panel in UL Type 1 Enclosure

Do not use for construction purposes. Refer to outline drawings for all construction details
Switch Amp Rating Height,inches With, inches Depth, inches Weight, lbs.
60 29 18 11.31 120
100 29 18 11.31 120
200 34 21.5 11.31 155
Accessories
Exerciser Clock kit, 7-day, electronic design, field installed. Part number: 300-5308

                                      

 